Chủ Nhật, 6 tháng 9, 2015

KFU8-GUT-Ex1.D

Công ty TNHH kỹ thuật công nghệ và dịch vụ Tiên Phong

D5 KDC Miếu Nổi, Đinh Tiên Hoàng, P3, Q.Bình Thạnh

Website:   www.pitesvietnam.com                                                       
                www.sensor-encoder.com                         

                www.pepperl-fuchs.com

Service and Support

Phone:          
0914 738 179
E-Mail:






Temperature Converter with Trip Values KFU8-GUT-Ex1.D

  • 1-channel isolated barrier
  • Universal usage at different power supplies
  • Thermocouple, RTD, potentiometer or voltage input
  • Redundant TC input
  • Current output 0/4 mA ... 20 mA
  • 2 relay contact outputs
  • Configurable by PACTware or keypad
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL2 acc. to IEC 61508/IEC 61511
Download the complete datasheet as a PDF:
ENG
 

Datasheet excerpt: Technical data of KFU8-GUT-Ex1.D

General specifications
Signal typeAnalog input
Supply
Connectionterminals 23, 24
Rated voltage20 ... 90 V DC / 48 ... 253 V AC
Power dissipation/power consumption≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Input
Connectionterminals 1, 2, 3, 4, 6 
RTDPt100, Pt500, Pt1000, Ni100, Ni1000
Types of measuring2-, 3-, 4-wire technology
Lead resistancemax. 50 Ω
Measuring circuit monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)
Cold junction compensationexternal and internal
Measuring circuit monitoringsensor breakage
Voltage0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV
Potentiometer0.8 ... 20 kΩ
Types of measuring2-, 3-, 5-wire technology
Input resistance≥ 250 kΩ (0 ... 10 V)
min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Measuring currentapprox. 400 µA with resistance measuring sensor
Output
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7-
Output I, IIrelay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIIAnalog current output
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)
Transfer characteristics
Sampling rateapprox. 700 ms
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Low voltage
Directive 2006/95/ECEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas
EC-Type Examination CertificateTÜV 03 ATEX 2140 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1) G [Ex ia] IIC
Ex-Hexagon II (1) D [Ex iaD]
Directive conformity
Directive 94/9/ECEN 60079-0:2009, EN 60079-11:2007, EN 60079-26:2007 , EN 61241-11:2006